5-11
For GT02, GT02L, GT03-E, GT05, GT12, GT32, GT32-R and GT32-E
Code No.
Content
Cause and solution
**0000
BCC error
1) The value of BCC may be incorrect. Check if there is no
calculation mistake.
2) There is a temporary error due to noise, etc. Re-supply power
to the PLC and GT.
**00FF
Time up error
1) The PLC connection cable is disconnected. Check the
connection cable to make sure it is connected.
2) There is a temporary error due to noise, etc. Re-supply power
to the PLC and GT.
**0100
Keyboard screen data
parts digit error
Check if the digit of the data parts on the keyboard screen has
been set correctly.
**0101
Alarm history error
When updating the alarm history display is stopped, alarm
history data displayed on the GTs screen has been updated
within the memory. Once the stop of display update is cancelled,
new data is displayed.
**0102
True Type font file
transfer error
Screen data is not transferred correctly. Re-transfer after
deleting all data.
**0500
Tool setting error
The device that cannot be used is specified for the data. Check
if the used device is correct. (e.g. the word device is set in the
bit area.)
**1000
SD memory card not
inserted
The SD memory card is not inserted to the SD memory card slot
properly. Check the SD memory card slot.
**1001
SD memory card
writing error
Data cannot be written to the SD memory card. Check whether
the SD memory card is not write-protected.
**1002
SD memory card
memory full
Data cannot be written as the memory of the SD memory card
has been exhausted. Delete some data in the SD memory card
or prepare a new SD memory card.
**1003
SD memory card
reading error
The data in the SD memory card cannot be read.
Check whether the saved data in the SD memory card is not
damaged with a PC.
**1004
SD memory card data
error
The data loaded from a SD memory card does not match the GT
type. Read the data in the SD memory card with GTWIN, and
check whether it is not damaged.
**1005
SD memory card
saved file name error
The file name to be saved to the SD memory card from the GT
is not specified properly. Specify the file name properly.
**1006
SD memory card
recognition error
The SD memory card cannot be recognized.
Check the SD memory card used.
**1020
PLC model unmatch
error
Check if the PLC program for transfer matches the destination
PLC.
**1021
PLC model
unsupported error
The selected PLC model is not supported. Confirm the PLC
model.
**1022
Password protection
error
(1) Incorrect passwords were input three times or more. Input
the correct password after turning the power supply off and then
on again.
(2) The upload protection has been set for the PLC.
(3) The number of digits was changed when setting a new
password with the FP monitor function. Cancel the password
setting first to change the number of digits.
**1023
Master memory
installation error
A master memory is installed in the PLC (FP-X).Programs
cannot be transferred to the PLC with the master memory from a
SD memory card.
**1024
Program memory
shortage
Program memory shortage in the destination PLC. Decrease the
program size using the PLC tool.

Table of Contents

Other manuals for Panasonic GT32

Related product manuals