3-5
3.1.4 UL/c-UL Qualification
Be aware of the following when applying for UL standard for the equipment that the GT has been
built in.
When the GT built in equipment, the GT should meet the standard as a part of the enclosure.
As the rear of the GT is not qualified as an enclosure, provide a fire enclosure (metal barrier) that
entirely covers the rear and lateral sides of the GT.
3.1.5 Mounting Screws
Secure the GT to a mounting plate using the fitting and screws provided with the unit.
Recommended screws
Recommended product
GT unit
Size
Others
Quantity
Mounting screw
GT01/GT11
M3 20
Material: SW pane-head (+)
Galvanization,
trivalent chromate
4 pcs/unit
GT05/GT21/GT32/
GT32-R/GT32-E
M3 25
GT02/GT02L/GT03-E/GT12 dedicated screw
The GT02/GT02L/GT03-E/GT12 dedicated screw is not sold on the open market.
Using screws other than the dedicated screw will cause failures such as decrease of water-proof
property.
Name
Content
Model No.
Attachment fitting
(with dedicated screws)
5 sets for GT02/GT02L/GT03-E/GT12
4 pcs of attachment fittings and 4 pcs of dedicated
screws/set