- Notes
· Select a circuit breaker (MCCB) and a noise filter with capacity appropriate for power supply capacity
(considering load conditions).
· Terminal block and ground terminal, Use copper conductor wires with a temperature rating of 75 ° C or higher for wiring.
The protective earth terminal is from size A to size E is M4, size F to size G is M5, size H is M6. If the tightening torque
of the screw exceeds the maximum value (refer to the terminal block explanation page), the terminal block may be damaged.
· The wire diameter of the ground wire is at least 2.0 mm 2 (AWG 14) at 50 W to 2.5 kW output, 3.5 mm 2 (AWG 12) or more
at 3.0 kW to 5.0 kW output, 7.0 kW at 8.0 mm 2 (AWG 8 ) Or more, please use 22 mm 2 (AWG 4) or more for output
15.0 kW and 38 mm 2 (AWG 2) or more for 22.0 kW output.
· Use the supplied dedicated connector from size A to E.
· Tighten the screw of the connecting connector (X4) to the host controller at a tightening torque of 0.3 to 0.35 N · m.
If it exceeds 0.35 N · m, the servo driver side connector may be damaged.