37
4. ELECTRICAL WIRING 
4-1. General Precautions on Wiring 
(1)  Before wiring, confirm the rated voltage of the unit as 
shown on its nameplate, then carry out the wiring closely 
following the wiring diagram. 
(2)  Provide a power outlet to be used exclusively for each unit 
and a circuit breaker for overcurrent protection should be 
provided in the exclusive line. 
(3)  To prevent possible hazards from insulation failure, the unit 
must be grounded. 
(4)  Each wiring connection must be done in accordance with 
the wiring system diagram. Wrong wiring may cause the 
unit to misoperate or become damaged. 
(5)  Do not allow wiring to touch the refrigerant tubing, 
compressor, or any moving parts of the fan. 
(6)  Unauthorized changes in the internal wiring can be very 
dangerous. The manufacturer will accept no responsibility 
for any damage or misoperation that occurs as a result of 
such unauthorized changes. 
(7)  Regulations on wire diameters differ from locality to 
locality. For field wiring rules, please refer to your LOCAL 
ELECTRICAL CODES before beginning. 
  You must ensure that installation complies with all relevant 
rules and regulations. 
(8)  To prevent malfunction of the air conditioner caused by 
electrical noise, care must be taken when wiring as follows: 
●  The remote control wiring and the inter-unit control wiring 
should be wired apart from the inter-unit power wiring. 
●  Use shielded wires for inter-unit control wiring between units 
and ground the shield on both sides. 
(9)  If the power supply cord of this appliance is damaged, 
it must be replaced by a repair shop designated by the 
manufacturer, because special-purpose tools are required. 
4-2. Recommended Wire Length and Wire Diameter 
for Power Supply System
Indoor unit
Type
(B) Power supply
Time delay fuse or 
circuit capacity
2.5 mm
2
U1, Y1, T1, F1, M1 Max. 130 m 10-16 A
E1 (73, 106, 140) Max. 60 m 10-16 A
E1 (224 / 280) Max. 50 / 30 m 10-16 A
Control wiring
(C) Inter-unit 
(between 
outdoor and 
indoor units) 
control wiring
(D) Remote 
control wiring
(E) Control 
wiring for 
group control
(F) Inter-
Outdoor unit 
control wiring
0.75 mm
2
(AWG #18)
Use shielded 
wiring*
0.75 mm
2 
(AWG #18)
0.75 mm
2 
(AWG #18)
0.75 mm
2
 
(AWG #18)
Use shielded 
wiring
Max. 1,000 m Max. 500 m
Max. 200 m 
(Total)
Max. 300 m
NOTE
*
 With ring-type wire terminal.
3-37. Important Note for Wiring 4-Way Cassette Type
(1) The power supply inlet is located at the lower area of 
the refrigerant tubing side of the unit. The electrical 
component box is located at the air intake of the bottom 
of the unit.
(2) Before installing the ceiling panel, be sure to carry out 
the wiring connection.
(3) Remove the lid located on the bottom of the indoor unit 
attaching the electrical component box by unscrewing 
the philip head tapping screws (x2).
(4) Lead the wires from the power supply inlet to the unit. 
Be sure to lead the wires through the power supply inlet. 
Make sure that no wire is caught between the indoor unit 
and ceiling panel. Otherwise, the unit may cause a fire.
(5) Connect the wires into the terminals through the power 
supply inlet for the electrical component box. 
Fix the wires with a clamping clip.
(6) Reinstall the lid of the electrical component box in its 
original position with paying attention not to have the 
wires caught in the lid.
Refer to “4. ELECTRICAL WIRING”.
Power supply inlet
Tapping screw position
Panaindoor336013Eng.indb37Panaindoor336013Eng.indb37 2012/03/2121:07:172012/03/2121:07:17