43
●  For the flare nuts at tubing connections, be sure to use the 
flare nuts that were supplied with the unit, or else flare nuts 
for R410A (type 2). The refrigerant tubing that is used must 
be of the correct wall thickness as shown in the table below. 
Tube diameter
Tightening torque
(approximate)
Tube thickness
ø6.35 (1/4")
14 – 18 N · m
(140 – 180 kgf · cm)
0.8 mm
ø9.52 (3/8")
34 – 42 N · m
(340 – 420 kgf · cm)
0.8 mm
ø12.7 (1/2")
49 – 61 N · m
(490 – 610 kgf · cm)
0.8 mm
ø15.88 (5/8")
68 – 82 N · m
(680 – 820 kgf · cm)
1.0 mm
ø19.05 (3/4")
100 – 120 N · m
(1000 – 1200 kgf · cm)
1.0 mm
  Because the pressure is approximately 1.6 times higher than 
conventional refrigerant pressure, the use of ordinary flare 
nuts (type 1) or thin-walled tubes may result in tube rupture, 
injury, or asphyxiation caused by refrigerant leakage.
●  In order to prevent damage to the flare caused by over-
tightening of the flare nuts, use the table above as a guide 
when tightening.
●  When tightening the flare nut on the liquid tube, use an 
adjustable wrench with a nominal handle length of 200 mm.
5-3. Insulating the Refrigerant Tubing
Tubing Insulation
●  Thermal insulation must be applied to all units tubing, 
including distribution joint (field supply).
 * For gas tubing, the insulation material must be heat 
resistant to 120°C or above. For other tubing, it must be 
heat resistant to 80°C or above.
  Insulation material thickness must be 10 mm or greater.
  If the conditions inside the ceiling exceed DB 30°C and RH 
70%, increase the thickness of the gas tubing insulation 
material by 1 step.
Two tubes arranged together
Liquid tubing
Gas tubing
Insulation
Fig. 5-7
CAUTION
If the exterior of the outdoor unit valves has been finished 
with a square duct covering, make sure you allow sufficient 
space to access the valves and to allow the panels to be 
attached and removed.
Taping the fl are nuts
Wind the white insulation tape around the flare nuts at the gas 
tube connections. Then cover up the tubing connections with 
the flare insulator, and fill the gap at the union with the supplied 
black insulation tape. Finally, fasten the insulator at both ends 
with the supplied vinyl clamps. (Fig. 5-8) 
Flare insulator (supplied)
Insulation tape (white)
(supplied)
Tube insulator 
(not supplied) 
Heat resistant 
120°C or above
Flare union
Flare nut
Unit side
Fig. 5-8
Insulation material 
The material used for insulation must have good insulation 
characteristics, be easy to use, be age resistant, and must not 
easily absorb moisture.
CAUTION
After a tube has been insulated, never try to bend it into 
a narrow curve because it can cause the tube to break or 
crack.
Never grasp the drain or refrigerant connecting outlets 
when moving the unit. 
5-4. Taping the Tubes
(1)  At this time, the refrigerant tubes (and electrical wiring 
if local codes permit) should be taped together with 
armoring tape in 1 bundle. To prevent condensation from 
overflowing the drain pan, keep the drain hose separate 
from the refrigerant tubing.
(2)  Wrap the armoring tape from the bottom of the outdoor 
unit to the top of the tubing where it enters the wall. As you 
wrap the tubing, overlap half of each previous tape turn.
(3)  Clamp the tubing bundle to the wall, using 1 clamp approx. 
each meter. (Fig. 5-9)
Insulated tubes
Drain hose
Clamp
Fig.5-9
NOTE
Do not wind the armoring tape too tightly since this will 
decrease the heat insulation effect. Also ensure that the 
condensation drain hose splits away from the bundle and drips 
clear of the unit and the tubing.
Panaindoor336013Eng.indb43Panaindoor336013Eng.indb43 2012/03/2121:07:192012/03/2121:07:19