47
7-3. Others
(1) Checking After Installation
 1)  Check that there are no gaps between the unit and 
the ceiling panel, or between the ceiling panel and the 
ceiling surface.
* Gaps may cause water leakage and condensation.
 2)  Check that the wiring is securely connected.
*  If it is not securely connected, the auto flap will not 
operate. 
(“P09” is displayed on the remote controller.) 
In addition, the water leakage and condensation may 
occur.
(2) Operating the Wireless Remote Controller
For details of installation, refer to the section “Wireless 
Signal Receiver” in the supplied installation instructions.
(3) Selecting DC Fan Motor Tap (4-Way cassette)
Check the optional parts accordingly in the following 
table.
Table for DC Fan Motor Tap Setting
Setting No.
Remote controller 
setting data 
Item code 5d
Contents & 
optional parts name
(3)
0003
Air-blocking material
(for 3-way air discharge)  
0003
Air-blocking material
(when a discharge  duct is 
connected) 
(6) 0006
Air-blocking material
(for 2-way air discharge) 
 *1  When using optional parts in different setting No. in 
combination with multiple units, conform it to the larger 
setting No.
 1)  When setting from the P.C. Board
      <Procedure>
      Stop the system before performing these steps.
   
1
 Open the electrical component box cover, then 
check the indoor unit control PCB.
   
2
 Connect the jumper connector (2P: yellow) 
which was supplied with the accessory to the 
correct connector pin on the indoor unit control 
PCB according to the setting number which was 
confirmed in Table for DC Fan Motor Tap Settings.
      Setting No. (3) :
   Then connect the jumper connector to the 
connector pin TP3 (2P: yellow) on the indoor unit 
control PCB.
      Setting No. (6) :
   Then connect the jumper connector to the 
connector pin TP6 (2P: white) on the indoor unit 
control PCB.
Fig. 7-10
  2) When setting with the Wired Remote Controller
      <Procedure>
      Stop the system before performing these steps.
   
1
 Press and hold the 
,   and   buttons 
simultaneously for 4 seconds or longer.
   
2
 If group control is in effect, press the 
 button 
and select the address (unit No.) of the indoor unit 
to set. At this time, the fan at the indoor unit begins 
operating.
   
3
 Designate the item code 
  by adjusting the 
Temperature Setting 
 /   buttons.
   
4
 Press the timer time 
 /   buttons to select the 
desired setting data.
*  For item codes and setting data, 
refer to “Table for DC Fan Motor Tap Setting”.
   
5
 Press the   button.
(The display stops blinking and remains lit, and 
setting is completed.)
  *  If air-blocking material is used, use the same 
procedure as in steps 
3
 – 
5
 above and change 
the setting for item code “62” to “0000.”
   If you wish to change the selected indoor unit, 
follow the step 
2
.
   
6
 Press the 
  button to return to normal remote 
controller display.
2
3
45
1
6