156
Auto address
3 Set.
(Select the Code no. [A1] and O/D unit no.)
▲ ▼ → ► →
(
Repeat
)
Code no. O/D unit no.
4
Press
After Selecting [YES], the unit restarts.
Code no. O/D unit no.
A1
Set the Auto address for each O/D unit no.
Select the O/D unit no. (outdoor unit) for Auto address.
Outdoor unit number
Attention
Set elec. consumption
3 Set.
(Select the power supply voltage of outdoor
units.)
▲ ▼ →
4 Select [YES].
Note
When 3-phase model connections are used for outdoor units
Power supply voltage Setting value
380 V 220 V
400 V 230 V
415 V 240 V
Set Auto address after all units are turned on and 90 seconds or more have passed.
Operate the units after Auto address is set and 90 seconds or more have passed.
Set the power supply voltage of outdoor units to calculate electric consumption of the Power consumption
monitor.
If the setting differs from the power supply voltage of outdoor units, the electric consumption value of the Power
consumption monitor will differ from the actual calculation result by a power meter.
Depending on the outdoor unit model, this cannot be set.