12
Item Unit Outdoor Unit
ø Three
V 400
Power Source (Phase, Voltage, Cycle)
Hz 50
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Input Power
kW Cooling: 3.56 Heating: 2.53 Heating: 3.49
Maximum Input Power For Heatpump System kW 7.91
Power Supply 1 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø / 11.9 / 7.91k
Power Supply 2 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) 3Ø / 13.0 / 3.00k
Power Supply 3 : Phase (Ø) / Max. Current (A) / Max. Input Power (W) — / — / —
Starting Current A 5.4
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
Running Current
A Cooling: 5.4 Heating: 3.9 Heating: 5.3
Maximum Current For Heatpump System A 11.9
Power Factor
Power factor means total figure of compressor and
outdoor fan motor.
% Cooling: 97 Heating: 96 Heating: 97
Number of core —
Power Cord
Length m (ft) —
Thermostat Electronic Control
Protection Device Electronic Control
Item Unit Indoor Unit
Performance Test Condition EN 14511
Outdoor Ambient °C
Cooling: 16 ~ 43
Heating: -20 ~ 35
Operation Range
Water Outlet °C
Cooling: 5 ~ 20
Heating: 25 ~ 55
Internal Pressure Differential kPa
Cooling: 23.1
Heating: 33.0
Condition
(Ambient/Water)
A35W7 A7W35 A2W35
dB (A) Cooling: 33 Cooling: 33 —
Noise Level
Power Level dB Cooling: 46 Cooling: 46 —
Height mm (inch) 892 (35-1/8)
Width mm (inch) 502 (19-3/4)
Dimension
Depth mm (inch) 353 (13-29/32)
Net Weight kg (lbs) 46 (101)
Liquid mm (inch) 9.52 (3/8)
Refrigerant Pipe Diameter
Gas mm (inch) 15.88 (5/8)
Inlet mm (inch) 28 (1-3/32)
Water Pipe Diameter
Outlet mm (inch) 28 (1-3/32)
Water Drain Hose Inner Diameter mm (inch) 15 (19/32)
Motor Type DC Motor
No. of Speed 7 (Software Selection)
Pump
Input Power W 60
Type Brazed Plate
No. of Plates 36
Size (W × H × L) mm 65 × 120 × 376
Hot Water Coil
Water Flow Rate l/min (m
3
/h)
Cooling: 28.7 (1.7)
Heating: 34.4 (2.1)
Pressure Relief Valve Water Circuit kPa Open: 300, Close: 265 and below
Flow Switch Magnetic Lead Switch
Protection Device A Residual Current Circuit Breaker (40)