EasyManua.ls Logo

Panasonic WH-SXC09F9E8

Panasonic WH-SXC09F9E8
161 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
135
16.5.34 Outdoor Defrost Temperature Sensor Abnormality (F43)
Malfunction Decision Conditions:
During startup and operation of cooling and heating, the temperatures detected by the outdoor defrost
temperature sensor are used to determine sensor error.
Malfunction Caused:
1 Faulty connector connection.
2 Faulty sensor.
3 Faulty outdoor unit PCB (main).
Abnormality Judgment:
Continue for 5 seconds.

Table of Contents

Other manuals for Panasonic WH-SXC09F9E8

Related product manuals