Switching/Blind Actuator
4.1.2 Parameters
Each channel has its own parameter page. For each channel only one function configuration can be set.
Possible functions include:
Switching
On/Off Delay
Pulse
Staircase light timer with pre-warning function
Depending on the function, the parameters listed below may change. The detailed functions are
explained after the function parameters.
4.1.2.1 Parameters on “Switching General” page
2min, 3min, 5min, 10min, 15min
20min, 30min, 45min, 60min
This parameter specifies the cycle time of feedback
object of each channel. The channel sends its own
state cyclically to the bus according to selected value.
No
Yes, only on change
Yes, cyclical and on change
Centralized feedback is a 4byte object that sends the
states of all channel to the bus. With these parameter
values the feedback type can be specified.
Cycle time for
centralized feedback
2min, 3min, 5min, 10min, 15min
20min, 30min, 45min, 60min
This parameter specifies the cycle time of central
feedback of all channel.
Use manual control
buttons
This parameter specifies whether the manual buttons
will be used or not for all Switching channels.