Switching/Blind Actuator
17
Name
Values
Description
Participation in central
switching
No: in no central object
Yes: in all central object
Only in central continuous On
Only in central continuous Off
Only in central switching
Only central switching and
continuous On
Only central switching and
continuous Off
Central continuous On and central
continuous Off
Defines which central objects the channel responds
to. The central objects have the following priority:
          
switched on regardless of the other objects.
If continuous ON is set to "0" and continuous OFF is
set to "1" then the channel is switched off regardless
of the other objects.
Central switching does not take priority over the
switching object the last command to be sent
applies.
The manual switches on the device take priority over
all bus commands.
Sending feedback
No
Yes,only on change,non-inverted
Yes,cyclical and on change, non-
inverted
Yes,only on change,inverted
Yes,cyclical and on change, inverted
This parameter sets whether the channel status will
be sent to the bus or not. If yes, the feedback type
can be set according to the values. The cycle time
can be set from the General page.
Behaviour at bus failure
Unchanged
ON
OFF
If the bus voltage has failed, then the channel adopts
the status defined here. The same applies to a
complete or partial download of the application.
Behaviour at mains
voltage or bus recovery
Like before failure
ON
OFF
After restoration of the mains supply or restoration
of the bus supply with the mains voltage present,
the channels revert to the status defined here.