Switching/Blind Actuator
33
Name
Value
Description
Response with safety:
Start/End
Safety ineffective
Upper end position / unchanged
Upper end position/ current
object value[%]
Upper end position/same as
before safety
Lower end position/ unchanged
Lower end position/ current
object value[%]
Lower end position/same as before
safety
Behaviour of the curtain on activation and
    

ends, the blind adjusts itself according to
%heigth and %slat object values.
Note: It does not make any sense to use the
setting "Current object value [%]" when
using the object "Comfort Automatic".
Assignment to safety
objects
Safety1
Safety2
Safety3
Safety1 and Safety2
Safety1 and Safety3
Safety2 and Safety3
Safety1, Safety2 and Safety3
This parameter defines whether the output
responds to a wind alarm and to which of
the alarms.
Participation in central
UP/DOWN object
No
Yes
This parameter defines whether the channel
is participated in central up/down function
or not.
Response on bus failure
Unchanged
Upper Final Position
Lower Final Position
After a bus failure (provided the mains
supply is present) the drive can be
driven to a preferred position (e.g.
"Open shutter").
Response to restoration of
bus and mains voltage
Unchanged
Upper Final Position
Lower Final Position
After restoration of the bus and mains the
drive can be driven to a preferred position
(e.g. "Open shutter") .