Paradox Magellan Systems   25
Table 7: Tamper Recognition Options
Tamper Bypass Options
Section [094]: Option [5]
Option [5] OFF = Ignore any tampers detected on a bypassed 
zone (default)
Option [5] ON =  Generate tamper if detected on a bypassed 
zone
• When option [5] is ON, the Tamper Recognition feature (see 
page 24) will ignore the zone’s bypass definition. This 
means the console will generate an incident as per the set 
Tamper Recognition option if a tamper occurs on a 
bypassed zone.
• When option [5] is OFF, the Tamper Recognition feature 
(see page 24) will follow the zone's bypass definition. This 
means the console will ignore any tampers that occur on a 
bypassed zone.
Wireless PGM Supervision Options
Section [218]: Options [1] to [4]; Wireless PGMs 1 to 4; Default: 
All ON
If enabled, Magellan can wait for each of its assigned MG-
2WPGM transmitters to send a status signal within a specified 
time (see Check-in Supervision Time on page 24) to confirm 
their presence and functionality. If a device has not sent a signal 
within the specified time period or Magellan tries to communicate 
with the device without success, Magellan can generate a 
trouble, an alarm and/or transmit a report code to the monitoring 
station as defined by the Wireless Transmitter Supervision 
Options (see page 24). Section [218] determines which wireless 
PGMs will be supervised and which will not. Enable the option 
pertaining to the MG-2WPGM you wish Magellan to supervise.
Backup Alarm Reporting Option
This feature provides you with the option of supervising the 
communication between the Magellan console and the MG-
2WPGM. If enabled, the MG-2WPGM will periodically check for 
communication with the Magellan console. If there is no 
response from the console, the relay will activate.
When the Magellan system is in entry delay, the console will 
send a message to the MG-2WPGM telling it that it is in entry 
delay. During the entry delay, the MG-2WPGM will check for 
communication with the Magellan console every 10 seconds and 
if there is no response from the console, the relay will activate.
To enable the backup reporting option:
1. Press [
MENU
] + [4] + [
INSTALLER
 
CODE
] + [7].
2. Using the [
NEXT
] key, scroll to the [
CONSOLE
 
SUPERV
?] 
option.
3. Press [
OK
].
Panic Alarms
Section [091]: Options [1], [2] and [3]
Option [1] OFF = Panic 1 (Emergency Panic) disabled (default)
Option [1] ON = Panic 1 (Emergency Panic) enabled
Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default)
Option [2] ON = Panic 2 (Auxiliary Panic) enabled
Option [3] OFF = Panic 3 (Fire Panic) disabled (default)
Option [3] ON = Panic 3 (Fire Panic) enabled
Enable section [091] options [1], [2] and [3] to enable the 
system’s three panic alarms. Each panic alarm is activated by 
pressing two keys simultaneously and holding them down for 2 
seconds. See Table 8 on page 25 for the appropriate panic 
alarm keys. Whether these panic alarms will generate a silent or 
audible alarm is determined by section [091] options [4] to [6] 
(see Panic Alarm Types on page 25).
Table 8: Panic Alarm Keys
Remote controls can also be programmed to generate panic 
alarms. See Programming the Remote Control’s Buttons on 
page 19 for more information on programming remote controls 
to generate panic alarms.
Panic Alarm Types
Section [091]: Options [4], [5] and [6]
Option [4] OFF = Panic 1 (Emergency Panic) is silent (default)
Option [4] ON = Panic 1 (Emergency Panic) is audible
Option [5] OFF = Panic 2 (Auxiliary Panic) is silent (default)
Option [5] ON = Panic 2 (Auxiliary Panic) is audible
Option [6] OFF = Panic 3 (Fire Panic) is silent (default)
Option [6] ON = Panic 3 (Fire Panic) is pulsed 
Options Description
[3] [4]
OFF OFF Tamper Recognition disabled (default)
OFF ON Trouble only
System armed or disarmed: If a tamper wiring failure 
occurs on a zone, the console will generate a trouble 
and send a report to the monitoring station (if 
programmed).
ON OFF Audible alarm when armed
System armed: 
If 
a tamper failure occurs on a zone, 
the console will follow the zone's Alarm Types setting 
(see page 16).
System disarmed: If a tamper failure occurs on a 
zone, the console will generate a trouble and send a 
report to the monitoring station (if programmed).
ON ON Audible alarm
System armed: If a tamper failure occurs on a zone, 
the console will follow the zone's Alarm Types setting 
(see page 16).
System disarmed: It functions the same as Trouble 
Only setting, except it will also generate an audible 
alarm.
Keys to press Panic Alarm Type
[1] and [3] Panic 1 (Emergency Panic)
[4] and [6] Panic 2 (Auxiliary Panic)
[7] and [9] Panic 3 (Fire Panic)