Paradox Magellan Systems 25
Table 7: Tamper Recognition Options
Tamper Bypass Options
Section [094]: Option [5]
Option [5] OFF = Ignore any tampers detected on a bypassed
zone (default)
Option [5] ON = Generate tamper if detected on a bypassed
zone
• When option [5] is ON, the Tamper Recognition feature (see
page 24) will ignore the zone’s bypass definition. This
means the console will generate an incident as per the set
Tamper Recognition option if a tamper occurs on a
bypassed zone.
• When option [5] is OFF, the Tamper Recognition feature
(see page 24) will follow the zone's bypass definition. This
means the console will ignore any tampers that occur on a
bypassed zone.
Wireless PGM Supervision Options
Section [218]: Options [1] to [4]; Wireless PGMs 1 to 4; Default:
All ON
If enabled, Magellan can wait for each of its assigned MG-
2WPGM transmitters to send a status signal within a specified
time (see Check-in Supervision Time on page 24) to confirm
their presence and functionality. If a device has not sent a signal
within the specified time period or Magellan tries to communicate
with the device without success, Magellan can generate a
trouble, an alarm and/or transmit a report code to the monitoring
station as defined by the Wireless Transmitter Supervision
Options (see page 24). Section [218] determines which wireless
PGMs will be supervised and which will not. Enable the option
pertaining to the MG-2WPGM you wish Magellan to supervise.
Backup Alarm Reporting Option
This feature provides you with the option of supervising the
communication between the Magellan console and the MG-
2WPGM. If enabled, the MG-2WPGM will periodically check for
communication with the Magellan console. If there is no
response from the console, the relay will activate.
When the Magellan system is in entry delay, the console will
send a message to the MG-2WPGM telling it that it is in entry
delay. During the entry delay, the MG-2WPGM will check for
communication with the Magellan console every 10 seconds and
if there is no response from the console, the relay will activate.
To enable the backup reporting option:
1. Press [
MENU
] + [4] + [
INSTALLER
CODE
] + [7].
2. Using the [
NEXT
] key, scroll to the [
CONSOLE
SUPERV
?]
option.
3. Press [
OK
].
Panic Alarms
Section [091]: Options [1], [2] and [3]
Option [1] OFF = Panic 1 (Emergency Panic) disabled (default)
Option [1] ON = Panic 1 (Emergency Panic) enabled
Option [2] OFF = Panic 2 (Auxiliary Panic) disabled (default)
Option [2] ON = Panic 2 (Auxiliary Panic) enabled
Option [3] OFF = Panic 3 (Fire Panic) disabled (default)
Option [3] ON = Panic 3 (Fire Panic) enabled
Enable section [091] options [1], [2] and [3] to enable the
system’s three panic alarms. Each panic alarm is activated by
pressing two keys simultaneously and holding them down for 2
seconds. See Table 8 on page 25 for the appropriate panic
alarm keys. Whether these panic alarms will generate a silent or
audible alarm is determined by section [091] options [4] to [6]
(see Panic Alarm Types on page 25).
Table 8: Panic Alarm Keys
Remote controls can also be programmed to generate panic
alarms. See Programming the Remote Control’s Buttons on
page 19 for more information on programming remote controls
to generate panic alarms.
Panic Alarm Types
Section [091]: Options [4], [5] and [6]
Option [4] OFF = Panic 1 (Emergency Panic) is silent (default)
Option [4] ON = Panic 1 (Emergency Panic) is audible
Option [5] OFF = Panic 2 (Auxiliary Panic) is silent (default)
Option [5] ON = Panic 2 (Auxiliary Panic) is audible
Option [6] OFF = Panic 3 (Fire Panic) is silent (default)
Option [6] ON = Panic 3 (Fire Panic) is pulsed
Options Description
[3] [4]
OFF OFF Tamper Recognition disabled (default)
OFF ON Trouble only
System armed or disarmed: If a tamper wiring failure
occurs on a zone, the console will generate a trouble
and send a report to the monitoring station (if
programmed).
ON OFF Audible alarm when armed
System armed:
If
a tamper failure occurs on a zone,
the console will follow the zone's Alarm Types setting
(see page 16).
System disarmed: If a tamper failure occurs on a
zone, the console will generate a trouble and send a
report to the monitoring station (if programmed).
ON ON Audible alarm
System armed: If a tamper failure occurs on a zone,
the console will follow the zone's Alarm Types setting
(see page 16).
System disarmed: It functions the same as Trouble
Only setting, except it will also generate an audible
alarm.
Keys to press Panic Alarm Type
[1] and [3] Panic 1 (Emergency Panic)
[4] and [6] Panic 2 (Auxiliary Panic)
[7] and [9] Panic 3 (Fire Panic)