ICEP002-005
6 Dépannage
PANNE
CAUSE
REMÈDE
LA TEMPÉRATURE DE
L’EAU EN SORTIE EST SUPÉ-
RIEURE À LA VALEUR PRO-
GRAMMÉE
LE COMPRESSEUR S’ARRÊTE EN
RAISON DE L’INTERVENTION DU PRES-
SOSTAT HAUTE PRESSION
ASPIRATION
COMPRESSEUR,
LIGNE LIQUIDE
GIVRÉES
LE COMPRESSEUR
FONCTIONNE
LONGUEMENT,
ET FAIT DU BRUIT
DÉBIT D’EAU
EXCESSIF, CHARGE THER-
MIQUE ÉLEVÉE
DIMINUER LE
DÉBIT DU FLUIDE À REFROI-
DIR
TEMPÉRATURE
AMBIANTE
ÉLEVÉE
RAMENER LA
TEMPÉRATURE AMBIANTE
SOUS LA VALEUR
LIMITE DÉCLARÉE
PRESSOSTAT
CASSÉ OU
DÉRÉGLÉ
REMPLACER LE
PRESSOSTAT
FILTRE
RÉFRIGÉRANT
COLMA
REMPLACER
LE FILTRE
AILETTES DU
CONDENSATEUR
SALES
NETTOYER LES
AILETTES DU
CONDENSATEUR
SURFACE DU CONDENSEUR
BOUCHÉE
LIBÉRER LA
SURFACE
FRONTALE DU
CONDENSATEUR
DÉBIT D’EAU
INSUFFISANT
AUGMENTER LE DÉBIT
DU FLUIDE À
REFROIDIR
COMPOSANTS DE
COMPRESSEUR
ENDOMMAGÉS
RÉPARER OU
REMPLACER LE
COMPRESSEUR
FUITES DANS LE
CIRCUIT,
INSTALLATION
DÉCHARGÉE
CONTRÔLER LA
PRÉSENCE DE
FUITES, LES ÉLIMINER,
CHARGER LE
CIRCUIT
FILTRE
RÉFRIGÉRANT
COLMA
REMPLACER
LE FILTRE
oui
non
oui
oui oui oui oui
oui
oui
oui
oui
non
non
non
non

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Parker Hiross Hyperchill Plus ICEP002 and is the answer not in the manual?

Parker Hiross Hyperchill Plus ICEP002 Specifications

General IconGeneral
BrandParker Hiross
ModelHyperchill Plus ICEP002
CategoryChiller
LanguageEnglish

Related product manuals