HOLDING
NUMBER
REGISTER
HOLDING REGISTER
DESCRIPTION
FUNCTION CODE 3
DETAILS
0 Software Version
1 Graphics Version
2 Run Time (Seconds)
3
4
ECO(DDS) Time
(Seconds)
5
6
Calculated ECO(DDS)
%
7
8
Display connection
Status
0: Not Connected 1: Connected
9 Dew Point
10 System Status 1
Bit 0: Dewpoint Alarm
Bit 1: Dewpoint Sensor Open Circuit
Bit 2: Dewepoint Sensor Short Circuit
Bit 3: Not Dened
Bit 4: Not Dened
Bit 5: Not Dened
Bit 6: Not Dened
Bit 7: Carbon Hours Warning
Bit 8: Filter Hours Warning
Bit 9: Desiccant Hours Warning
Bit10: Catalyst Hours Warning
Bit 11: Carbon Hours Alarm
Bit 12: Filter Hours Alarm
Bit 13: Desiccant Hours Alarm
Bit 14: Catalyst Hours Alarm
Bit 15: Invalid DIP Switch Settings
11 System Status 2
Bit 0: Remote Stop Mode Active
Bit 1: Purge Economy Mode Active
Bit 2: Purge Setting Mode Active
Bit 3: Filter DP Alarm Active
Bit 4: SCA Alarm Active
Bit 5: Unused
Bit 6: Dewpoint Sensor Fault
Bit 7: I2C Sensor Fault
Bit 8: I2C Magic Number Fault
Bit 9: I2C Sensor Overrange Fault
Bit10: BAS Mode Active
Bit 11: BAS Mode Cong Fault
Bit 12: Unused
Bit 13: Unused
Bit 14: Unused
Bit 15: Unused
12
ADS Cong:
Hygrometer Minimum
Output
Range: -120C to +40C
13
ADS Cong:
Hygrometer Range
Range: 50 to 150
14
ADS Cong: Startup
Dewpoint Alarm Delay
Range: 0 to 240 minutes
15
ADS Cong:Dewpoint
Fault Time Delay
Minutes
Range: 0 to 60 minutes
16
ADS Cong: Custom
Dewpoint Alarm oset
Range: -120C to + 120C
17
ADS Cong: Moisture
Override Period
Range: 0 to 240 minutes
18
ADS Cong: Moisture
Override Half Cycles
Range: 0 to 10
HOLDING
NUMBER
REGISTER
HOLDING REGISTER
DESCRIPTION
FUNCTION CODE 3
DETAILS
19
ADS Cong: Custom EST
Setpoint
Range: -120C to 0C
20
ADS Cong: Service
Interval (Filter)
500 to 30,000Hours
21
ADS Cong: Inlets N/O
On Standby
0: O 1: On
22
ADS Cong: Separate
Dewpoint Alarm Output
0: O 1: On
23
ADS Cong: Selected
Cycle
0: 6 mins 1: 4 mins 2: Custom
24
ADS Cong: Moisture
Override Cycle Number
0: Disabled
>0 Active (No. MO Cycles)
25
26
IADS Cong: IST Sensor
Bias
27
ADS Cong: MODBUS
Baud Rate
Range: 9600, 19200
or 38400 Baud
28
ADS Cong: MODBUS
Parity
Range: 0 (None), 1 (Odd),
2 (Even)
29
ADS Cong:
MODBUS Stop Bits
Range: 1 or 2
30
ADS Cong: Custom Cycle
Side A Exhaust On Time
Range: 0 to 1800s
31
ADS Cong: Custom Cycle
Side A O Time
Range: 0 to 1800s
32
ADS Cong: Custom Cycle
Side A Exhaust O Time
Range: 0 to 1800s
33
ADS Cong: Custom Cycle
Side B Exhaust On Time
Range: 0 to 1800s
34
ADS Cong: Custom Cycle
Side B O Time
Range: 0 to 1800s
35
ADS Cong: Custom Cycle
Side B Exhaust O Time
Range: 0 to 255
36
ADS Cong: Modbus
Address
Range: 0 to 255
MODBUS Strings Continued..
34