HEATLESS DESICCANT
COMPRESSED AIR DRYER
MODEL’S 75 - 6000
S/N
INSTALLATION, OPERATION
& MAINTENANCE MANUAL
Service Department
1-800-451-6023

Questions and Answers

  • I
    imartinAug 18, 2025
    Why is my Parker Dehumidifier not turning on (no lights)?
    • R
      Richard SimpsonAug 18, 2025
      Your Parker Dehumidifier might not be turning on because of a blown control fuse (replace the fuse), no power supply (apply correct power), or an inoperative solid state controller (replace the controller).
  • W
    Whitney GarciaAug 20, 2025
    What to do if Parker Dehumidifier has excessive pressure drop?
    • J
      Joseph HendersonAug 20, 2025
      If your Parker Dehumidifier has an excessive pressure drop, the pre-filter is likely dirty (replace the element), the afterfilter is dirty (replace the element), or the desiccant is dirty (replace the desiccant).
  • A
    Ashley WrightAug 26, 2025
    What to do if Parker Dehumidifier lights are on, but the dryer doesn't switch?
    • C
      cathyjohnsonAug 26, 2025
      If the lights are on but your Parker Dehumidifier isn't switching, it could be due to a control air shutoff (open the valve), the dryer being in PowerLoc, CycleLoc, or ProPurge mode, or the dryer not being in a 100% load cycle (check the setting). For PowerLoc, CycleLoc, or ProPurge modes consult pages 9-10.
  • S
    Stephanie Long MDAug 27, 2025
    How to fix excessive air loss on the regenerating tower of Parker Dehumidifier?
    • R
      Robin MontgomeryAug 27, 2025
      Excessive air loss on the regenerating tower of your Parker Dehumidifier could be due to: * Purge set too high (check specifications and adjust). * Repressurization solenoid leaking (repair or replace). * Inlet valve leaking or not functioning (repair or replace). * Leaking or inoperative control solenoid (repair or replace). * Defective controller (repair or replace).
  • T
    Thomas ParkerAug 30, 2025
    Why Parker Dehumidifier unit does not fully repressurize?
    • R
      Reginald BrownAug 30, 2025
      If your Parker Dehumidifier unit does not fully repressurize, it could be due to a purge rate that is too low (adjust purge), leaking exhaust valves (see above), a faulty repressurization solenoid (replace solenoid), or a plugged purge or repressurization orifice.
  • C
    Christopher BarnesSep 1, 2025
    How to eliminate back pressure in regenerating tower in Parker Dehumidifier?
    • C
      Caroline ShortSep 2, 2025
      To eliminate back pressure in the regenerating tower of your Parker Dehumidifier, you should check for clogged mufflers (clean, repair, or replace), leaking check valves (clean, repair, or replace), a purge flow that is too high (adjust), or no output from the controller (replace fuse or controller).
  • C
    Carol PerezSep 3, 2025
    What causes inlet or exhaust valves not functioning in Parker Dehumidifier?
    • S
      Susan ButlerSep 4, 2025
      Inlet or exhaust valves not functioning on your Parker Dehumidifier can be caused by bad diaphragms or O-rings (rebuild valves available kits or replace), no control air (see below), defective control solenoids (repair or replace), or no output from the controller (repair or replace).
  • C
    Cynthia PetersonSep 6, 2025
    What to do if the exhaust valve on drying or repressurizing tower is leaking in Parker Dehumidifier?
    • C
      Crystal LeSep 6, 2025
      If the exhaust valve on the drying or repressurizing tower of your Parker Dehumidifier is leaking, it could be because the valve is dirty (clean valve), the diaphragms or O-rings are defective (repair or replace), or the control solenoid is leaking (repair or replace).
  • M
    melinda83Sep 8, 2025
    How to troubleshoot no control air at inlet or exhaust valves in Parker Dehumidifier?
    • H
      hicksjasonSep 8, 2025
      If there's no control air at the inlet or exhaust valves of your Parker Dehumidifier, check if the control air shutoff valve is closed (open it), the control air filter is dirty (replace element), there's a leak in the control air tubing (repair), the control solenoid is defective (repair or replace), or there's no output from the controller (replace fuse or controller).
  • S
    stevenbowenSep 12, 2025
    What causes Parker Dehumidifier failure to switch?
    • N
      nelsontamiSep 12, 2025
      A failure to switch in your Parker Dehumidifier can be caused by a time delay setting that is too short (adjust properly, Failure to Switch option only!). It may also be related to the dryer not operating (see above).

Summary

Installation and Inspection

Dryer Location

Guidelines for selecting an appropriate and accessible location for the dryer.

Installation

Key steps and requirements for correctly installing the dryer.

Safety and System Precautions

General Operation

Sequence of Operation

Start Up

Shutdown Procedures

Demand Cycles

Maintenance Program

Daily Maintenance

Routine checks to be performed daily for optimal dryer performance.

Desiccant Replacement

Parts (General Parts Description)

Spare Parts Lists

Lists of replacement parts for various dryer models by CFM.

Trouble Shooting Guide

High Humidity

PowerLoc System

Quick-Start for Dryers Equipped with Powerloc

Steps for initial setup and operation of the Powerloc system.

Troubleshooting Chart

Warranty

Warranty Procedure

Outlines the steps for initiating a warranty claim or repair.

Parker Airtek TW 25 Specifications

General IconGeneral
BrandParker
ModelAirtek TW 25
CategoryDehumidifier
LanguageEnglish

Related product manuals