Medium Flow Compressed Air Dryers - IOMI.
Changing MODBUS communication Settings Via ADS Service Software
Important Note:
After changing any parameters, the control board must be power cycled (Power o / Power On) for the changes to be accepted.
To change the baud rate on the CDAS HL /OFAS HL / FBP HL dryers it is necessary to connect the dryer to a PC using the Parker ADS
service software to communicate with the control board.
Once the dryer is connected and the ADS software
started, navigate to the SETTINGS tab.
Left click on ‘MODBUS baud rate.
is will open a second window which will allow
you to change the baud rate to match that of the
MODBUS system.
e settings for MODBUS Parity, MODBUS Stop Bits and MODBUS Address (Unit ID or Node) are selected and changed in the same
way to match the MODBUS system parameters.