Connect via branch protection fuses, filter (optional), 3 semi-conductor fuses, contactor, 
capacitor box (optional), and AC Line Choke/Reactor.  
Refer to Manual Specification E 
Connect shield between motor and earth rail:   
Connect shield between motor and earth rail . These terminals provide an internal motor 
field supply fused by 10A (Frame 1) / 20A (Frame 2) fuses.   
Note the nominal field current from the motor rating plate  
The range can be set to 5A or 20A/10A by the switch SW1 in the Power Board,  
The setting of the field current range switch (SW1) must not be changed when the drive is 
powered on, and the P- code may need to be reset. 
 
Single phase, 110/240V ac, 50/60Hz. 
Match auxiliary supply to the contactor coil voltage. Protect with external fuses determined by 
the contactor holding VA, or MCB. 
Connect auxiliary supply terminals directly to the incoming supply. No series sequencing 
switches or contacts are permitted without consultation from Parker 
Connect the contactor coil to terminals CL1& CL2 
Connect motor thermal switch or thermistor to TH1, TH2. Drive will trip when the thermal 
switch opens, or when the thermistor resistance exceeds 4k maximum (PTC Type A: IEC 
34-11 Part 2). If the motor does not have a protective device (thermistor), link these 
terminals. 
Thermistor inputs must be connected for the drive to run.