2: Calibrating the Control Board 
2.1  CONNECT THE AUXILIARY SUPPLY: Remove 3-phase fuses (6). Re-instate branch circuit protection or circuit 
breaker (8). Check that the auxiliary voltage is correct. The Keypad will now display the Welcome screen. 
AUXILIARY POWER ONLY IS CONNECTED AT THIS STAGE 
  Press ,  ,   to display the CONFIGURE DRIVE menu. Press   again to display 
the first parameter. Set the following parameters in the menu: 
Set to ENABLED. All LEDS on the Keypad will flash. 
Enter Armature Voltage value (VACAL) from the motor rating 
plate 
Enter the armature current value (IA CAL) from the motor 
rating plate. 
Enter the nominal field current (IF CAL) from the motor rating 
plate. 
Check that the field control mode is set to VOLTAGE 
CONTROL. 
Enter the calculated ratio into the parameter given by the 
equation. The default setting of 90% is the maximum value 
obtainable, i.e. field output = 0.9 x Vac. 
Set to DISABLED. The Keypad's LEDs will stop flashing. 
Exit the CONFIGURE DRIVE menu and press the   (UP) 
key to display the PARAMETER SAVE menu. Press  . 
Press the   (UP) key as instructed to save your settings.  
Refer to 3.3. 
Refer to the 
Product Code on 
the drive's Rating 
Label to confirm 
the drive's 
specification.