•ChooseNext to set RPI.
•ChooseFinish. Notice that the PSSCCNA is now under the I/O
configuration.
If your RSLogic 5000 is Version 13.X:
•Choosethe1738-ACNR/A from the list of modules.
•Enteraname,anappropriatenodeaddress,andchassissize.
Make sure to choose Compatible Module for Electronic Keying
setting.
•ChooseNext to set RPI.
•ChooseFinish. Notice that the 1738-ACNR is now under the
I/O configuration
H Series Fieldbus ControlNet Adapter, Series A (PSSCCNA) E103P
4
Set the Node Address
To set the node address, adjust the switches on the front of the
module (refer to the illustration on page 1). Use a small blade
screwdriver to rotate the switches. Line up the small notch on the
switch with the number setting you wish to use. The two switches
are most significant digit (MSD) and least significant digit (LSD).
The switches can be set from 01 through 99. The module reads the
switches at power-up only.
The rotary switches are read periodically. If the switches have been
changed since the last time they were read and they no longer match
the on line address, a minor fault will occur, which is indicated by a
flashing red Adapter Status LED.
EDS File Requirements
The EDS file is available online at www.parker.com/pneu/
hseriesfieldbus
This example shows the
node address set at 63.
Add ControlNet Adapter to RSLogix 5000
I/OConguration
To add your PSSCCNA to RSLogix 5000 I/O configuration, follow
these steps:
•InRSLogix5000,highlighttheControlNet Scanner, right click
and select New Module.
If your RSLogic 5000 is Version 15.X or greater:
•ChoosethePSSCCNA module from the list of Parker modules.
•Enteraname,anappropriateaddressandchassissize.