SettheNetworkAddress
To set the network address, you can:
• Adjusttheswitchesonthefrontofthemodule
• UseaDynamicHostCongurationProtocol(DHCP)server
• RetrievetheIPaddressfromnonvolatilememory
The adapter reads the switches first to determine if the switches are
set to a valid number. You set the node address by adjusting the 3
switches on the front of the module (refer to the illustration on page
1). Use a small blade screwdriver to rotate the switches. Line up the
small notch on the switch with the number setting you wish to use.
Valid settings range from 001 through 254.
When the switches are set to a valid number, the adapter’s IP address
will be 192.168.1.xxx (where xxx represents the number set on the
switches). The adapter’s subnet mask will be 255.255.255.0 and the
gateway address will be set to 0.0.0.0. When the adapter is reading
the network address set on the switches, the adapter will not have a
host name assigned to it or use any Domain Name System.
If the switches are set to an invalid number (i.e., 000 or a value
greater than 254), the adapter checks to see if DHCP is enabled.
If DHCP is enabled, the adapter asks for an address from a DHCP
server. The DHCP server will also assign other Transport Control
Protocol (TCP) parameters.
If DHCP is not enabled, the adapter will use the IP address (along with
other TCP configurable parameters) stored in nonvolatile memory.
EDS File Requirements
The EDS file is available online at www.parker.com/pneu/
hseriesfieldbus
H Series Fieldbus EtherNet/IP Adapter, Series A (PSSCENA) E104P
4
This example shows
the network address
set at 163.
Add EtherNet/IP Adapter to RSLogix 5000
I/OConguration
To add your PSSCENA to RSLogix 5000 I/O configuration, follow
these steps:
•InRSLogix5000,highlighttheEtherNet/IP Scanner, right click
and select New Module.
If your RSLogic 5000 is Version 15.X or greater:
•ChoosethePSSCENA module from the list of Parker modules.
•Enteraname,anappropriateI/Paddressandchassissize.
•ChooseNext to set RPI.
•Choose Finish. Notice that the PSSCENA is now under the I/O
configuration.
If your RSLogic 5000 is Version 13.X:
•Choosethe1738-AENT/A from the list of modules.
•Enteraname,anappropriateIPaddress,andchassissize.Make
sure to choose Compatible Module for Electronic Keying
setting.