EtherNet/IPAdapter-PSSCENA
ExpansionI/OCapacity • Maximumof63modules
• Maximumof5RackOptimizedconnections(fordigitalmodulesonly)
• Maximumof25Directconnections
•
PSSCENA backplane current output = 1.0A maximum. The actual number of modules
can vary. Add up the current requirements of the modules you want to use to make sure
they do not exceed the amperage limit of 1.0A for the PSSCENA.
•
Backplane current can be extended beyond 1.0A with a PSSSE24A Backplane Extension
Power Supply. Add multiple PSSSE24A modules to reach the 63 module maximum.
Cat. No. PointBus Current Requirements
PSSN8xxx 75 mA
PSSP8xxx 75 mA
PSST8xxx 75 mA
PSSTR4M12A 90 mA
PSSNACM12A 75 mA
PSSNAVM12A 75 mA
PSSTACM12A 75 mA
PSSTAVM12A 75 mA
PSSS23A 75 mA
PSSV32A 75 mA
EtherNet/IP Communication Rate 10/100Mbits /s, half or full-duplex
PowerSupplySpecications
Power Supply Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a
NEC Class 2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV)
power supply to power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak
or 60VDC under normal conditions and under single fault conditions. A PELV supply has
the same rating and is connected to protected earth.
Input Voltage Rating 24VDC nominal
10-28.8VDC range
Inrush Current 6A maximum for 10ms
Field Side Power Requirements, Maximum 24VDC (+20% = 28.8VDC) @ 400 mA
Interruption Output voltage will stay within specifications when input drops out for
10ms at 10V with maximum load
GeneralSpecications
LED Indicators 1 green/red Adapter status
1 green Network activity
1 green/red Network status
1 green/red PointBus status
1 green System Power (PointBus 5V power)
1 green Adapter Power (24V from field supply)
Power Consumption, Maximum 8.1W @ 28.8VDC
Power Dissipation, Maximum 2.8W @ 28.8VDC
Thermal Dissipation, Maximum 9.5 BTU/hr. @ 28.8VDC
PointBus Output Current, Maximum 1A @ 5VDC ±5% (4.75 - 5.25)
Input Overvoltage Protection Reverse polarity protected
Isolation Voltage 50V rms
(continuous-voltage withstand rating) Tested to withstand 1250VAC rms for 60s
Field Power Bus
Nominal Voltage 24VDC
Supply Voltage 10-28.8VDC range
Supply Current 10A maximum
Dimensions Inches (Millimeters) 4.41H x 2.83W x 2.56D (112H x 72W x 65D)
H Series Fieldbus EtherNet/IP Adapter, Series A (PSSCENA) E104P
7
Specications
Following are specifications for the PSSCENA EtherNet/IP adapter.