H Series Fieldbus EtherNet/IP Adapter, Series A (PSSCENA) E104P
6
TroubleshootwiththeIndicators
EtherNet I/P
PSSCENA
Adapter
Status
Network
Activity
Network
Status
PointBus
Status
System
Power
Adapter
Power
X10
X100
PWR
X1
P
A
D
D
R
E
S
S
I
PSSCENA
Adapter Status
Indicator
Network Activity
Indicator
Network Status
Indicator
PointBus Status
Indicator
System Power
Indicator
Adapter Power
Indicator
Indication Probable Cause
Adapter Status
Off No power applied to device
Flashing
Red/Green
LED power up test (module self-test)
Green Device is operating normally
Flashing Red Recoverable fault has occurred:
- Firmware (NVS) update
- Network IP address changed
- CPU load exceeded
Solid Red Unrecoverable fault has occurred:
- Self-test failure (checksum failure
at power up, ramtest) failure at
power up
- Firmware fatal error
Indication Probable Cause
NetworkActivity
Off No link established
Flashing Green/Off Transmit or receive activity
Green Link established
Indication Probable Cause
NetworkStatus
Off Device is not initialized. The module
does not have an IP address.
Flashing Green No CIP connections. Device has an IP
address, but no CIP connections are
established.
Green
CIP connections. Device on line, has an
IP address, and CIP connections are
established.
Flashing Red One or more Ethernet
®
connections
has timed out.
Red No link. The module is not physically
connected to a powered Ethernet
device.
Flashing Red/Green The module is performing a self test
(only occurs during power up test).
Indication Probable Cause
PointBus Status
Off Device not powered -
check module status indicator
Flashing Red/Green Recoverable fault has occurred:
- At power up the number of
expected modules does not equal
the number of modules present
- A module is missing
- Node fault (I/O connection timeout)
Red Unrecoverable fault has occurred:
- The adapter is bus off
- Controller in program/idle mode
- Ethernet cable open
Green Adapter is on line with connections
established (normal operation,
run mode)
Indication Probable Cause
SystemPower*
Off Not active - Field power is off,
overloaded backplane or dc-dc
converter problem
Green System power on - dc-dc converter
active (5V)
Indication Probable Cause
AdapterPower**
Off Not active - Field power is off
Green Power on - 24V present
* System Power Indicator shows the 5V power output from the dc-dc converter.