H Series Fieldbus 24 VDC Input Modules, Series A
E106P
6
Add 24 VDC Input Modules to RSLogix 5000
I/OConguration
To add your input modules to RSLogix 5000 I/O configuration, follow
these steps:
•InRSLogix5000:
- For ControlNet, highlight the PSSCCNA or 1738-ACNR
(Shown), right click and select New Module.
Communicate With Your Module
I/O messages are sent to (consumed) and received from (produced)
the I/O modules. These messages are mapped into the processor’s
memory. These I/O input modules produce 1 byte of input data
(scanner Rx - status). They do not consume I/O data (scanner Tx).
DefaultDataMapfortheInputModules
PSSN8M8A, PSSN8M12A, PSSN8M23A,
PSSP8M8A, PSSP8M12A, PSSP8M23A
Message Size: 1 Byte
7 6 5 4 3 2 1 0
Produces
(Scanner Rx)
Ch7 Ch6 Ch5 Ch4 Ch3 Ch2 Ch1 Ch0
Channel
Status
Where:0=OFF,1=ON
- For EtherNet/IP, highlight the PSSCENA or 1738-AENT
(Shown), right click and select New Module.
If your RSLogic 5000 is Version 15.X or greater:
•Choose the PSSN8M8A module from the list of Parker
modules.
•EnteranameandclickOK.
•NoticethatthePSSN8M8AisnowundertheI/Oconguration.
EDS File Requirements
The EDS files are available online at www.parker.com/pneu/
hseriesfieldbus
7 6 5 4 3 2 1 0
Produces 0 Ch3 Ch2 Ch1 Ch0
Channel
Status
Produces 1 Ch11 Ch10 Ch9 Ch8
Channel
Status
Where:0=OFF,1=ON
PSSP16M12A
Message Size: 2 ByteS