Indication Probable Cause
NetworkStatus
Off Device is not on line:
- Device has not completed
dup_MAC-id test.
- Device not powered
- check module status indicator.
Flashing Green Device is on line but has no
connections in the established state.
Green Device is on line and has connections
in the established state.
Flashing Red One or more I/O connections in
timed-out state.
Red Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green
Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication Probable Cause
I/O Status
Off Input is in the off state
Yellow Input on
If your RSLogic 5000 is Version 13.X:
•ChoosetheequivalentRockwellAutomationmodulefromthelist
of modules.
H Series Fieldbus
Modules
EquivalentRockwellAutomation
1738 ArmorPoint Modules
PSSN8M8A 1738-IB8M8
PSSN8M12A 1738-IB8M12
PSSN8M23A 1738-IB8M23
PSSP8M8A 1738-IV8M8
PSSP8M12A 1738-IV8M12
PSSP8M23A 1738-IV8M23
PSSN16M12A 1738-1B16DM12A
•
Enter a name (optional), slot number, and communication format.
Make sure to choose Compatible Module for Electronic Keying
setting.
•ChooseNext to set RPI.
•ChooseFinish. Notice that the input module is now under the
I/O configuration
H Series Fieldbus 24 VDC Input Modules, Series A
E106P
7
Troubleshoot With the Indicators
MOD
NET
PSSN8M12A
24V dc In
0
1
2
3
4
5
6
7
0
1
2
3
4
5
6
7
PSSN8M12A
I/O Status Indicators
Module Status Indicator
Network Status Indicator
Indication Probable Cause
Module Status
Off No power applied to device
Green Device operating normally
Flashing Green Device needs commissioning due
to missing, incomplete, or incorrect
configuration
Flashing Red Recoverable fault
Red Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test