EasyManua.ls Logo

Parker H Series - Page 79

Parker H Series
344 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
H Series Fieldbus 24 VDC Analog Input Modules, Series A (PSSNACM12A, PSSNAVM12A) E110P
8
Analog Input Modules
Inputs per Module 2 single ended, nonisolated
Input Voltage PSSNAVM12A only
0-10V (user configurable) (-0.0V under, +0.5V over)
±10V (user configurable) (-0.5V under, +0.5V over)
Input Current PSSNACM12A only
4-20 mA
0-20 mA
Input Impedance PSSNACM12A - 60
PSSNAVM12A - 100k
Resolution PSSNACM12A - 16 bits - over 0-21 mA; 0.32µA/cnt
PSSNAVM12A - 15 bits plus sign; 320µV/cnt in unipolar or bipolar mode
Absolute Accuracy
1
0.1% Full Scale @ 25°C
Accuracy Drift w/Temp. PSSNACM12A - 30ppm/°C
PSSNAVM12A - 5ppm/°C
Input Update Rate (per module) 100 ms @ Notch = 60 Hz (default)
120 ms @ Notch = 50 Hz
24 ms @ Notch = 250 Hz
12 ms @ Notch = 500 Hz
Step Response (per module) 70 ms @ Notch = 60 Hz (default)
80 ms @ Notch = 50 Hz
16 ms @ Notch = 250 Hz
8 ms @ Notch = 500 Hz
Digital Filter Time Constant 0-10,000 ms (default = 0 ms)
Input Resistance PSSNAVM12A only
200k
Conversion Type
Delta Sigma
Common Mode Rejection Ratio
120 dB
Normal Mode Rejection Ratio
-60 dB
-3 dB
Notch filter
15.7 Hz @ Notch = 60 Hz
13.1 Hz @ Notch = 50 Hz
65.5 Hz @ Notch = 250 Hz
131 Hz @ Notch = 500 Hz
Data Format Signed integer
GeneralSpecications
Maximum Overload Fault protected to 28.8VDC
Calibration Factory calibrated
Indicators 1 green/red module status indicator, logic side
1 green/red network status indicator, logic side
2 green/red input status indicators, logic side
KeyswitchPosition 3
PointBus Current 75 mA @ 5VDC
Power Dissipation PSSNACM12A - 0.6W @ 28.8VDC
PSSNAVM12A - 0.75W @ 28.8VDC
Thermal Dissipation, Maximum PSSNACM12A - 2.0 BTU/hr. @ 28.8VDC
PSSNAVM12A - 2.5 BTU/hr. @ 28.8VDC
Isolation Voltage 50V rms
(continuous voltage withstand rating) Tested at 1250VAC rms for 60s
External DC Power
Supply Voltage 24VDC nominal
Voltage Range 10-28.8VDC
Supply Current PSSNACM12A - 10 mA @ 24VDC; PSSNAVM12A - 15 mA @ 24VDC
Dimensions Imperial (Metric) 1.25H x 2.63W x 4.25D (31.75H x 66.80W x 107.95D)
Operating Temperature IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock):
-20 to 60°C (-4 to 140°F)
Storage Temperature IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),
IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),
-40 to 85°C (-40 to 185°F)
Relative Humidity IEC 60068-2-30 (Test Db, Un-packaged Non-operating Damp Heat): 5 to 95% non-condensing
Shock IEC60068-2-27 (Test Ea, Unpackaged Shock):
Operating 30g
Non-operating 50g
Vibration IEC60068-2-6 (Test Fc, Operating): 5g @ 10 to 500Hz
ESD Immunity IEC 61000-4-2: 6kV contact discharges, 8kV air discharges
Radiated RF Immunity IEC 61000-4-3:
10V/m with 1kHz sine-wave 80%AM from 30MHz to 2000MHz
10V/m with 200Hz 50% Pulse 100%AM at 900Mhz
10V/m with 200Hz 50% Pulse 100%AM at 1890Mhz
EFT/B Immunity IEC 61000-4-4: ±3kV at 5kHz on signal ports
Surge Transient Immunity IEC 61000-4-5: ±2kV line-earth(CM) on shielded ports
Conducted RF Immunity IEC 61000-4-6: 10Vrms with 1kHz sine-wave 80%AM from 150kHz to 80MHz
Emissions CSPR 11: Group 1, Class A
Enclosure Type Rating Meets IP65/66/67 (when marked)
Mounting Base Screw Torque #8 screw, 7.5 in. lbs. in Aluminum, 16 in. lbs. in Steel
Wiring Category
2
1 - on signal ports
Weight Imperial (Metric) 0.637 lb. (0.289 kg)
Certifications: c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada
(when product is marked) CE
European Union 89/336/EEC EMC Directive, compliant with:
EN 61000-6-4; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial Requirements
EN 61000-6-2; Industrial Immunity
C- Tick Australian Radiocommunications Act, compliant with:
AS/NZS CISPR 11; Industrial Emissions
1. Includes offset, gain, non-linearity and repeatability error terms.
2. Use this Conductor Category information for planning conductor routing. Refer to Publication E115P, “Industrial Automation Wiring and Grounding Guidelines”.
Specications -
Following are specifications for the PSSNACM12A and PSSNAVM12A analog input modules.