If your RSLogic 5000 is Version 13.X:
•ChoosetheequivalentRockwellAutomationmodulefromthelist
of modules.
HSeriesFieldbus EquivalentRockwellAutomation
Modules 1738 ArmorPoint Modules
PSSNACM12A 1738-IE2CM12
PSSNAVM12A 1738-IE2VM12
•
Enter a name (optional), slot number, and comm. format. Make
sure to choose Compatible Module for Electronic Keying
setting.
•ChooseNext to set RPI.
•ChooseFinish. Notice that the analog input module is now under
the I/O configuration
H Series Fieldbus 24 VDC Analog Input Modules, Series A (PSSNACM12A, PSSNAVM12A) E110P
7
Troubleshoot With the Indicators
MOD
NET
PSSNACM12A
Analog Current
In
0
1
0
1
PSSNACM12A
I/O Status Indicators
Module Status Indicator
Network Status Indicator
Indication Probable Cause
Module Status
Off No power applied to device
Green Device operating normally
Flashing Green Device needs commissioning due to
missing, incomplete, or incorrect
configuration
Flashing Red Recoverable fault
Red Unrecoverable fault -
may require device replacement
Flashing Red/Green Device is in self-test
Indication Probable Cause
NetworkStatus
Off Device is not on line:
- Device has not completed
dup_MAC-id test.
- Device not powered - check module
status indicator.
Flashing Green Device is on line but has no
connections in the established state.
Green Device is on line and has
connections in the established state.
Flashing Red One or more I/O connections in
timed-out state.
Red Critical link failure - failed
communication device. Device
detected error that prevents it from
communicating on the network.
Flashing Red/Green
Communication faulted device - the
device has detected a network access
error and is in communication faulted
state. Device has received and accepted
an Identity Communication Faulted
Request - long protocol message.
Indication Probable Cause
I/O Status
Off Module in CAL mode
Solid Green Normal (channel scanning inputs)
Flashing Green Channel being calibrated
Solid Red No power or major channel fault
Flashing Red
Channel at end of range (over or under)