H Series Fieldbus 32 Point Valve Driver, Series A (PSSV32A) E100P
7
TroubleshootWiththeIndicators
Mod
PSSV32A
Net
Fault
PSSV32A
Module Status
Indicator
Network Status
Indicator
Output Fault Status
Indicator
Indication Probable Cause
Module Status
Off No power applied to device
Green Device operating normally
Flashing Green Device needs commissioning due to missing, incomplete, or incorrect configuration
Flashing Red Recoverable fault
Red Unrecoverable fault - may require device replacement
Flashing Red/Green Device is in self-test
Indication Probable Cause
NetworkStatus
Off
Device is not on line:
- Device has not completed dup_MAC-id test.
- Device not powered - check module status indicator.
Flashing Green Device is on line but has no connections in the established state.
Green Device is on line and has connections in the established state.
Flashing Red One or more I/O connections in timed-out state.
Red
Critical link failure - failed communication device. Device detected error that prevents it from
communicating on the network.
Flashing Red/Green
Communication faulted device - the device has detected a network access error and is in
communication faulted state. Device has received and accepted an Identity Communication
Faulted Request - long protocol message.
Indication Probable Cause
Output Fault Status
Off Outputs operating normally
Red Over current, short circuit or over temperature detected on one or more outputs. (On-State only)