7.3 Techincal data
12
ICEP007-024 (60Hz)
Address Display label App type Default Min Max Unit Read Only Note
9251 QEFA BOOL 0 TRUE Fan output
9252 AFHE BOOL 0 TRUE Output antifreeze resistor
9253 HECA BOOL 0 TRUE Compressor carter resistor output
9254 QEHE BOOL 0 TRUE Output Electric resistor in Control Panel
9255 AOF INT %R.H. TRUE Analog output for fan speed control
9256 B1 INT °C/°F TRUE B1 °F if C_F=0, B1 °C if C_F=1
9257 B2 INT °C/°F TRUE B2 °F if C_F=0, B2 °C if C_F=1
9258 B3 INT °C/°F TRUE B3 °F if C_F=0, B3 °C if C_F=1
9259 B10 INT °C/°F TRUE B10 °F if C_F=0, B3 °C if C_F=1
9260 B8 INT bar TRUE Pressure
9300 ER01 USINT TRUE Probe B1 error
9301 ER02 USINT TRUE Probe B2 error
9302 ER03 USINT TRUE Probe B3 error
9303 ER04 USINT TRUE High pressure alarm 1 from pressure switch
9304 ER05 USINT TRUE Low pressure alarm 1 from pressure switch
9305 ER06 USINT TRUE Pump thermal alarm
9306 ER07 USINT TRUE Low level H2O tank alarm
9307 ER08 USINT TRUE Probe B8 error
9308 ER09 USINT TRUE High pressure alarm 2 from pressure switch
9309 ER10 USINT TRUE Probe B10 error
9310 ER11 USINT TRUE Low pressure alarm 2 from pressure switch
9311 ER12 USINT TRUE Compressor protection 1 alarm
9312 ER13 USINT TRUE Compressor protection 2 alarm
9313 ER14 USINT TRUE High temperature alarm 1 from H2O task output
9314 ER15 USINT TRUE Low temperature alarm 1 from H2O task output
9315 ER16 USINT TRUE High temperature alarm 2 from H2O task output
9316 ER17 USINT TRUE Low temperature alarm 2 from H2O task output
9317 ER18 USINT TRUE Ambient high temperature warning
9318 ER19 USINT TRUE Ambient low temperature warning
9319 ER20 USINT TRUE NOT USED
9320 ER21 USINT TRUE Compressor 1 extrawork warning
9321 ER22 USINT TRUE Compressor 2 extrawork warning
9322 ER23 USINT TRUE Phase alarm
9323 ER24 USINT TRUE Unit extra work warning
9324 ER25 USINT TRUE Expansion alarm
9325 ER26 USINT TRUE RTC Warning
9002 ER27 USINT TRUE Pump thermal alarm 2
9400 HysP UINT 0 0 39 FALSE Historical Record: 0=Most Recent 39=Oldest
9401 HysC INT TRUE Historical Alarm Code
9402 Hysd INT TRUE Historical Alarm Date
9403 Hyst INT TRUE Historical Alarm Time
9404 Hys1 INT °C/°F TRUE Historical Alarm B1 Value
9405 Hys2 INT °C/°F TRUE Historical Alarm B2 Value
9406 Hys3 INT °C/°F TRUE Historical Alarm SET Value
9407 HisF UINT TRUE Historical Number of Records
9408 RESH BOOL 0 FALSE Reset request for alarm history
9461 Uer UINT TRUE Software Version