Parker RAC Europe    PSD04 | User manual ver. 3.6 | Code 144PSDI364 
 
Page 14 of 74 
 
 
Power supply 
Terminal  Meaning 
V≅+ 
power supply device (not isolated; 24 VAC +10% -15%, 50/60 Hz ±3 Hz, 40 VA max. or
24... 37 VDC, 22 W max.) 
V≅- 
power supply device (not isolated; 24 VAC +10% -15%, 50/60 Hz ±3 Hz, 40 VA max. or
24... 37 VDC, 22 W max.) 
 
  -  protect the power supply with a fuse rated 2 A-T 250 V 
  -  if the device is powered in direct current, it is necessary to respect the polarity of the power supply 
voltage. 
 
RS-485 port (not available in model PSD4BX3) 
Non optoisolated RS-485 port, with MODBUS communication protocol. 
Terminal  Meaning 
GND ground 
RS485+  D1 = A = + (terminal 1 of the transceiver) 
RS485-  D0 = B = - (terminal 0 of the transceiver) 
 
  -  connect the RS-485 MODBUS port using a twisted pair. 
For the settings about the RS-485 MODBUS port look at chapter 7 “CONFIGURATION”. 
 
RS-485 port line termination (not available in model PSD4BX3) 
Position microswitch 1 on position on (120 W, 0.25 W) to plug in the RS-485 port line termination (plug in the 
termination of the first and of the last element of the network). 
 
 
 
High voltage digital input 
High voltage digital input (if present). 
Part  Meaning 
DIHV1  high voltage digital input (optoisolated contact; 115 VAC -10%... 230 VAC +10%) 
DIHV1  high voltage digital input (optoisolated contact; 115 VAC -10%... 230 VAC +10%)