Parker RAC Europe PSD04 | User manual ver. 3.6 | Code 144PSDI364
Page 19 of 74
6 OPERATION
6.1 Switch on and resynchronization
At switch-on and after a resynchronization, the fundamental parameters for moving the motor are acquired.
The parameters of pressure and temperature units of measure are loaded at switch-on, and, if necessary, is performed
the conversion of all the parameters of pressure and temperature.
The parameters that are loaded only during the initialisation phase, and therefore require a reset to be loaded, are
referred to as manufacturer parameters (Manufacturer menu) and can be modified only in the stand-by state.
To select the desired valve, it is necessary to set the correct value in Valve selection (parameter Pi07).
All relevant parameters specific to that valve are loaded automatically from the flash memory, according to the table
below:
Pi07
Valve name
Minimum regulation
steps [step]
Maximum
regulation
steps [step]
Overdriving
steps [step]
Stepping
rate [step/s]
Operating phase
current [mA]
Holding phase
current [mA]
Recommended Step
Mode
CABLAGGIO
SO1A
SO1B
SO2A
SO2B
0* Generic valve Pr50 Pr51 Pr52 Pr53 Pr54 Pr55
1 Sporlan SER AA 0 2500 3500 400 120 0
FullStep
green red black white
2 Sporlan SER A 0 2500 3500 400 120 0
FullStep
green red black white
3 Sporlan SER B 0 2500 3500 400 120 0
FullStep
green red black white
4 Sporlan SER C 0 2500 3500 400 120 0
FullStep
green red black white
5 Sporlan SER D 0 2500 3500 400 120 0
FullStep
green red black white
6 Sporlan SERI F 0 2500 3500 400 120 0
FullStep
green red black white
7 Sporlan SERI G 0 2500 3500 400 120 0
FullStep
green red black white
8 Sporlan SERI J 0 2500 3500 400 120 0
FullStep
green red black white
9 Sporlan SERI K 0 2500 3500 400 120 0
FullStep
green red black white
10 Sporlan SERI L 0 2500 3500 400 120 0
FullStep
green red black white
11 Sporlan SEHI 175 0 6386 6500 400 160 0
FullStep
green red black white
12 Sporlan SEHI 400 0 6386 6500 400 160 0
FullStep
green red black white
13 Sporlan ESX 24 224 300 40 460 0
FullStep
green red black white
14 Sporlan EDEV B/C (U) 0 800 1250 200 120 0 FullStep ?? ?? ?? ??
15 Sporlan reserved -- -- -- -- -- -- -- -- -- -- --
16 Sporlan reserved -- -- -- -- -- -- -- -- -- -- --
17* Sporlan SER 1.5 to 20 0 1596 3500 400 160 0
FullStep
green red black white
18* Sporlan SEI 30 0 3193 6500 400 160 0
FullStep
green red black white
19* Sporlan SEI 50 0 6386 7500 400 160 0
FullStep
green red black white
20* Sporlan SEH 100 0 6386 7500 400 160 0
FullStep
green red black white
21* Sporlan SEI 0.5 to 11 0 1596 3500 400 160 0
FullStep
green red black white
22* Alco EXM/EXL-246 16 250 350 45 130 0
HalfStep
blue yellow white orange
23* Alco EX4 TO 6 0 750 1000 500 500 100
FullStep
blue brown white black
24* Alco EX7 0 1600 2000 500 750 250
FullStep
blue brown white black
25* Alco EX8 0 2600 3250 500 800 500
FullStep
blue brown white black
26* Danfoss ETS 12.5-25-50 0 2625 3150 300 100 75
FullStep
green red white black
27* Danfoss ETS 100 -250 0 3530 4250 300 100 75
FullStep
green red white black
28* Danfoss ETS 400 0 3810 4550 300 100 75
FullStep
green red white black
39***
*
Sprlan CO2 valve 0 2500
2750
/
3125
400 275 0
FullStep
green red white black