MIC 1400 Manual Edition 1
26
DISPLAY AVAILABLE FACTORY
STEP DESCRIPTION CODE SETTINGS SETTING
1 Input Select inPS See App. D* 1420
2 Output 1 Action Out1 Reverse REV
Direct
3 Alarm 1 Type ALA1 P_hi =Proc High P_hi
nonE=No Alarm
bAnd=Band
dE =Deviation
P_Lo=Proc Low
4 Alarm 2 Type ALA2 Same selection as nonE
ALA1
5 Output 2 Usage USE2 Out2 =Control Out2
(opposite of Out1 action)
LP_r =Loop Reverse
LP_d=Loop Direct
Ad_r =Rev Logic AND
Ad_d=Dir Logic AND
Or_r =Rev Logic OR
Or_d =Dir Logic OR
A2_r =Alm Rev
A2_d=Alm Dir
6 Output 3 Usage USE3 Al_d =Alm Dir Al_d
rEcP =Rcdr Out P.V.
rEcS =Rcdr Out S.P.
LP_r =Loop Reverse
LP_d=Loop Direct
Ad_r =Rev Logic AND
Ad_d=Dir Logic AND
Or_r =Rev Logic OR
Or_d=Dir Logic OR
Al_r =Alm Rev
7 Com Bit Rate CbS 1200, 2400, 4800, 4800
9600

Related product manuals