MIC 1400 ManualEdition 1 47
Decimal Point
This parameter, applicable only if a linear input is specified, defines the
position of the decimal point in values for the process variable, setpoint,
alarm levels and retransmission outputs as follows:
Value Decimal Point Position
0 XXXX
1 XXX.X
2 XX.XX
3 X.XXX
The default value is 0. Display code is dPoS.
Direct Logic OR
"ALM" flashes
Relay On
"ALM" Off
Relay Off
"ALM" flashes
Relay On
ALARM 1
VALUE
ALARM 2
VALUE
SP
PV
ALARM 1 TYPE - Deviation
ALARM 2 TYPE - Deviation
Reverse Logic OR
"ALM" flashes
Relay Off
"ALM" Off
Relay On
"ALM" flashes
Relay Off
ALARM 1
VALUE
ALARM 2
VALUE
SP
PV
ALARM 1 TYPE - Deviation
ALARM 2 TYPE - Deviation
ASYMMETRICAL BAND ALARM