Installer manual Autotrol Magnum 293 - 298 Logix 742-762 - Programming
Ref. MKT-IM-012 / D - 03.02.2022 49 / 110
6.3 Basic programming
Info
Menus are displayed in a defined and incremental order.
6.3.1 Basic programming mode chart 742-762/298 valve type
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
Program valve
type
255, 263, 268,
278 and
Magnum series
None N/A -
Program system
size
5 - 100 / F None liters -
Time setting 1:00 - 12:59AM
0:00 - 23:59PM
12:00PM hour:
minute
-
Day of week N/A None N/A -
Regeneration time 1:00 - 12:59AM
0:00 - 23:59PM
2:00AM hour:
minute
-
Days override (762
controller only)
0.5 - 99 0 day 0 = no days override.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
Days between
regeneration (742
controller only)
0.5 - 99 0 day 0 = no days between regeneration.
0.5 = regeneration twice a day at
time of regeneration and 12 hours
later.
Amount of brine
used per
regeneration
50-290 110 g/l -
Estimated system
capacity
N/A None kg
equivalent
CACO
3
For information purpose only on
the 742 controller.
Hardness (762
controller only)
30 - 2000 250 Mg/l
equivalent
CACO
3
-