58 / 110 Ref. MKT-IM-012 / D - 03.02.2022
Info
Parameters P16 to P19 are skipped on 742 controller.
6.4.3 Basic programming parameters (3 - Cycle filter system)
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
P1 Time of day 1:00 - 12:59
AM
0:00 - 23:59
PM
12:00 PM Hour :
minute
Range depends on value
selected for P10.
P2 Day of week N/A None N/A -
P3 Time of
regeneration
1:00 -
12:59AM
0:00 -
23:59PM
2:00 AM Hour :
minute
Range depends on value
selected for P10.
P4 Calendar
override
0 - 99 3 Days 0 = no calendar override.
0.5 = regeneration twice a day at
time of regeneration and
12hours later.
Calendar override skipped if at
least one day of regeneration
selected.
P5 Day of week
regeneration
N/A None N/A Day of week regeneration is
skipped if calendar override is
more than 0 (742 controller
only).
P6 Backwash time 1 - 250 14 Minutes -
P7 Capacity of unit 1 - 900 * m
3
Unit of measure depends on
value selected for P9.
P8 - - - - Skipped for 3 - cycle filter
configuration.
* Default value selected with valve type and resin volume.
6.4.4 Advanced programming parameters (3 - Cycle filter system)
Parameter
description
Range of
values
Default
value
Units of
measure
Notes
P9 Units of measure 0 - 1 ** N/A 0 = US unit.
1= Metric unit.
P10 Clock mode 0 - 1 ** N/A 0 = 12 hours clock.
1 = 24 hours clock.
P11 Service interval 0 - 250 0 Month Uses 30 days for each month.