Connection of the thermostat
The thermostat must be connected to 230VAC
according to the circuit diagrams. When using
multiple heating cables, totalling over 13A, a
contactor with integrated suppression device must
be used. If the protective earth terminal, PE, on the
thermostat is used, the incoming power cable to the
heating cable should be connected to the common
earth terminal on the thermostat, otherwise a
separate terminal connection block (not included )
must be used.
Product specific information for use with
floorheating systems
• Use with T2QuickNet:
T2QuickNet is approved with the thermostat
working in floor sensor mode. Be aware that the
floor sensor must be installed and activated for
an installation with T2QuickNet.
• Use with T2Red (T2Reflecta) self-regulating
systems:
Self-regulating heating cables have an inrush
current at start up. In order to guarantee the life
time of the thermostat, the maximum load of the
self-regulating application in nominal conditions
is limited to 10A.
A 13A self-regulating load will reduce the life
time of the relay contacts.