After allowing the temperature
of the floor to stabilise, the set
temperature value can be
calibrated against the real
floor / room temperature. This
needs to be done using a separate thermometer for
determining the actual floor or room temperature.
The thermo-meter should be put on the floor
surface, sensing the floor surface or on the wall
sensing the air temperature.
Floor regulation: the user can adjust the difference
between the temperature inside the floor and the
room temperature.
Room temperature =
Floor temperature (menu 2) – Offset (menu 3)
Change the temperature value via < > buttons
to the same value shown on the reference wall
thermometer.
Confirm by pressing <
> button.
Calibration of floor sensing mode <
>
In floor sensing mode there is a default offset value
of +4°C between the floor sensor and the floor
surface (which is the set value on the display).
The read-out value in Menu 2 can be used to assist
in calculating the required offset value. Change the
offset value via <
> buttons so that the set
temperature value will be approx. the same value as
shown on the reference floor surface thermometer.
Confirm by pressing <
> button.