In the summer time, in this 'OFF mode', the
thermostat acts as a thermometer only.
To go to the "OFF mode" use the arrow buttons to
scroll through the menu to activate P Symbol and
press <
> button. Select program (see page 12)
and press <
> button to choose Standby mode
.
The off mode is available only after the end of the
"First warming" function and after the learning
function. When one of these functions is in progress
the thermostat can power up the floor warming
system even if the thermostat is in off mode.
Deactivate Standby mode
• Use the < > buttons to scroll through the
menu and activate P
• The display switches to this view:
and OFF is flashing.
• Select program EcoHome, EcoOffice or °C
Comfort mode by using <
> buttons and
confirm by pressing <
>.
8. TROUBLE SHOOTING
8.1 Error codes
Number Error type
ER 1
Wrong floor sensor (100 kΩ)
ER 2
Short circuit on floor sensor
ER 3
Open circuit on floor sensor
ER 4
Short circuit on room sensor
ER 5
Open circuit on room sensor
ER 6
Other error
8.2 Monitoring of the temperature sensor
In the event of damage or malfunction of one of the
temperature sensors, the heating output cuts off (fail