21
thermometer for determining the actual floor or room
temperature. The thermometer should be put on the
floor surface, sensing the floor surface temperature,
or on the wall sensing the air temperature.
Calibration of room sensor mode < >:
In room sensor mode the internal sensor value is the
same as for the set value on the display.
Push the confirmation button <
> in 6 sec. to
enter the Configuration mode.
Push the confirmation button <
> to enter menu
number 2.
Change the temperature value via <
>
buttons to the same value shown on the reference
wall thermometer.
Push confirmation button several times (scroll
through Menu structure) to return to Normal mode
• Room sensor: Room temperature flashing and
possibility to adjust the room temperature with
<
> keys.
Initial value to calibrate
Calibration of floor sensor mode < >:
In floor sensor mode there is a default offset value
of +4°C between the infloor sensor value and the
floorsurface value (which is the set value on the
display). The read-out value in Menu 1 can be used
for set value calibration.
Push the confirmation button <
> in 6 sec. to
enter the Configuration mode.
Push again the confirmation button <
> to enter
menu number 2.
Change the offset value via < > buttons so that the
set temperature value will be approx. the same value shown
on the reference floor surface thermometer.