24
Before the last day, the thermostat
powers the floor heating system during
19 minute on each 24 min cycle (= 19h
of warming the first day).
The last day, the thermostat powers
the floor heating system during
20 minute on each 24 min cycle
(= 20h of warming the first day).
If the thermostat regulation works with the floor
sensor only, the
cement slab temperature will be
limited to 20°C.
If the thermostat regulation works with the room
sensor only, the ambient temperature will be
limited to 20°C.
In both cases of power supply failure or main switch
put on ‘Off’ position by the user during this function
progress, the thermostat will resume from where
it stopped ("First warming" function time saved in
memory).
This function can be stopped at any
time by setting the installer menu
number 4 to ‘OFF’
At the end of this "First warming" function, the learning
function begins if room sensor mode is activated.
5.3.6 Menu 6: Heating Running Time
Running time (the time in the course of which the
floor warming system is powered)
3’ : 3 minutes
[0..59] 5h : 5 hours [1..23]
7d : 7 days [1..30]
The sensor mode is detected and initialised
automatically.
If the floor sensor cable is connected, it operates in
floor sensor mode.
To reset this time the user has to press <
>
simultaneously for more than 3 seconds.