Loading...
06 I VFD-4000 VFD-4000 I 07
Size and Frame
External Dimensions (IP 55 Type)
VFD-4000 Installation
0.75~3.7kW (1~5HP) Unit: mm
Unit: mm5.5~18.5kW (7.5~25HP)
Item W L H
0075 208.6 199.9 280.0
0150 208.6 199.9 280.0
0220 208.6 199.9 280.0
0370 208.6 199.9 280.0
Item W L H
0550 208.6 199.9 360.0
0750 208.6 199.9 360.0
1100 208.6 199.9 360.0
1850 208.6 199.9 360.0
W
H
L
VFD-4000
VFD-4000
Drive Capacity
Thickness of Wires
mm2 (AwG)
R, S, T U, V, W
0.75kW 2.5 sq 2.5 sq
1.5kW 2.5 sq 2.5 sq
2.2kW 2.5 sq 2.5 sq
4kW 2.5 sq 2.5 sq
5.5kW 2.5 sq 2.5 sq
7.5kW 2.5 sq 2.5 sq
11kW 4.0 sq 4.0 sq
15kW 4.0 sq 4.0 sq
18.5kW 4.0 sq 4.0 sq
22kW 6.0 sq 6.0 sq
Wire Specifications