6500 Series Purge and Pressurization System
I/O Manual
12
Display 2x20 LCD for configuration, monitoring, and status
of the 6500 system with back light and contrast
selecting
Pneumatic parameters
Protective gas supply Instrument grade air or inert gas
Pressure requirement For 6500-MAN-DV: 1.4 to 8.3 bar (20 to 120 psig)
- regulated.
For 6500-MAN-PV: 3.5 to 6.9 bar (50 to 100 psig)
-regulated.
Note: max pressure will depend on the vent model
used.
Safe pressure Gas: 0.88 mbar (0.35” wc)
Dust: 0.88 mbar (0.35” wc)
Gas+Dust: 0.88 mbar (0.35” wc)
Note: Gas and dust are not covered by the

Valve flows
EPV-6500-__-01, 03, 05 Standard vent series
Readout on display from 56 to 850 l/min (2 to 30
scfm) in increments of 28 l/min (1 scfm). Minimum
and maximum reading depend on type of vent and
supply pressure.
See data sheet for EPV-6500 series vent.
 Continuous (dilution) vent series

to 8 scfm) continuous reading. Maximum reading
depends on type of vent and supply pressure.
See data sheet for EPV-6500 series vent.
Communication output RS485, (PACTware available)
Ambient conditions
Ambient temperature 
Storage temperature 
Relative humidity 5 … 85%, noncondensing
Vibration resistance 5 … 100 Hz, 1g, 12 m/s², all axes
Impact resistance 30 g, 11 ms, all axes
Mechanical specifications
Connection types See mounting and cable gland requirements
Degree of protection IP66
Continued on next page