Segurança e harmonia
ININTERRUPTA
EN
6. Specifications
48
* Derate capacity to 60% of capacity in Frequency converter mode and to 80% when the output voltage is adjusted to 208VAC.
MODEL PH 9210 PH 9220 PH 9230
CAPACITY *
1000 VA / 800W 2000 VA / 1600 W 3000 VA / 2400 W
INPUT
Voltage
Range
160VAC/140VAC/120VAC/110VAC± 5 %
(based on load %: 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)
Low Line Transfer
Low Line Comeback
High Line Transfer
High Line Comeback
175 VAC ± 5 % or 85 VAC ± 5 %
300 VAC ± 5 % or 150 VAC ± 5 %
290 VAC ± 5 % or 145 VAC ± 5 %
40Hz ~ 70 Hz
Frequency Range
Single phase with ground
Phase
≧ 0.99 @ 220-230 VAC or 110-120 VAC
Power Factor
OUTPUT
208/220/230/240VAC
Output voltage
± 3%
AC Voltage Regulation (Batt. Mode)
47 ~ 53 Hz o 57 ~ 63 Hz
Frequency Range
(Synchronized Range)
50 Hz ± 0.25 Hz or 60Hz ± 0.3 Hz
Frequency Range (Batt. Mode)
100%~110%: audible warning
110%-130%: UPS shuts down in 30 seconds at battery mode or transfers to bypass mode
when the utility is normal.
>130%: UPS shuts down immediately at battery mode or transfer to bypass mode when
the utility is normal.
Overload
3:1Current Crest Ratio
Harmonic Distortion
≦ 4 % THD (linear load)
≦ 7 % THD (nonlinear load)
Tempo
trasfer
AC Mode to Batt. Mode
Inverter to Bypass
Zero
4 ms (Typical)
Pure SinewaveWaveform (Batt. Mode)
EFFICIENCY
AC Mode
≦ 3 % THD (linear load)
≦ 6 % THD (nonlinear load)
~ 85%
~ 83%
~ 88%
Battery Mode
BATTERY
Standard
Model
Battery Type
Numbers
Recharge Time
Charging Current
Charging Voltage
PHYSICAL
Tower
Dimension, Pr X An X Al
Net Weight (kg)
ENVIRONMENT
Operation Humidity (non-condensing)
Noise Level
MANAGEMENT
Smart RS-232 or USB
Optional SNMP
PH 9230
6000 VA / 4200 W
~ 90%
~ 85%
Uninterruptable Power Supply
PH 9210 | PH 9220 | PH 9230 | PH 9260
12 V / 7 AH 12 V / 9 AH 12 V / 9 AH
3 4 6
8 hours recover to 90% capacity (Typical)
1.0 A(max.)
397 X 145 X 240 (mm)
11
35.3
20-90 % RH @ 0- 40°C
< 45dBA @ 1 meter
Supports Windows® 98/2000/2003/XP/Vista/2008/ 7, Linux, Unix and MAC
Power management from SNMP manager and web browser
12 V / 10 AH
8
41.0 VDC ± 1% 52.0 VDC ±1% 109.4 VDC ±1%
426 X 190 X 318 (mm)
20-90 % RH @ 0- 40°C
< 55dBA @ 1 meter
82.1 VDC ±1%
16 28