EasyManuals Logo

Pilz PNOZ s7 User Manual

Pilz PNOZ s7
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
PNOZ s7
Operating Manual PNOZ s7
21399-EN-10
12
Operation
NOTICE
The safety function should be checked after initial commissioning and each
time the plant/machine is changed. The safety functions may only be
checked by qualified personnel.
LEDs indicate the status and errors during operation:
LED on
Status indicators
IN1
Channel1 actuated.
IN2
Channel2 actuated.
IN1, IN2, OUT
Safety contacts are closed.
Error indicators
FAULT
Diagnostics: Plug terminator not connected
} Remedy: Insert plug terminator, switch supply voltage off and then on
again.
Faults - malfunctions
} Contact malfunctions: If the contacts have welded, reactivation will not be possible after
the input circuit has opened.