PZEX4P
OperatingManualPZEX4P
1003201EN08
7
Wiring
Pleasenote:
}
Informationgiveninthe"Technicaldetails[ 9]"mustbefollowed.
}
Theoutputs1314,2324,3334and4344aresafetycontacts.
}
Topreventcontactwelding,afuseshouldbeconnectedbeforetheoutputcontacts(see
Technicaldetails).
}
Calculationofthemax.cablerunsl
max
intheinputcircuit:
R
lmax
=max.overallcableresistance(seeTechnicaldetails)
R
l
/km=cableresistance/km
}
Usecopperwirethatcanwithstand60/75°C.
}
Sufficientfuseprotectionmustbeprovidedonalloutputcontactswithcapacitiveandin
ductiveloads.
}
Donotswitchlowcurrentsusingcontactsthathavebeenusedpreviouslywithhighcur
rents.
Preparingforoperation
Supplyvoltage AC DC
Inputcircuit Singlechannel Dualchannel
Baseunit:
SafetyrelayPNOZX
Drivenviasafetycontacts
Baseunit:
SafetyrelayPNOZmulti
Drivenviasemiconductoroutputs
(24VDC)
Feedbackloop Baseunit:SafetyrelayPNOZX Baseunit:SafetyrelayPNOZmulti
Y1,Y2andInputareinputson
thebaseunit;theyevaluatethe
feedbackloop