22 - ATR224 - DRR224 - User manual
45
c. d e.1
Command Delay 1
Command delay (only in ON / OFF functioning).
-:..: mm:ss. Default: :.
Negative: delay when turning off output.
Positive: delay when turning on output.
46
c.S. p.1
Command Setpoint Protection 1
Allows or not to modify command setpoint value
FrEE
Modification allowed (Default)
Lock
Protected
F R.i N.
Free Initialized. At start, setpoint 1 of command 1 is initialized to the value set on
parameter 51
i.S P.1
(Initial Value Setpoint 1).
48
a . m a.1
Automatic / Manual 1
Enables the automatic/manual selection for command
diS a b.
Disabled (Default)
Ena b.
Enabled
En.S to.
Enabled with memory
49
i ni .S.
Initial State
Choose the state of the controller when turning it on. This only works on the RS version or by
enabling the Start/Stop from digital input or SET button.
Start
Start (Default)
stop
Stop
S t o r e.
Stored. State of Start/Stop prior to switching off.
51
i .SP.1
Initial Value Setpoint 1
Determines the initial value (at start) of setpoint of command when
F R.i N.
is selected on
parameter
c. S . p.1
(Command Setpoint Protection )
-..+ [digit
p.
] (degrees for temperature sensors). Default .
52÷53 Reserved Parameters - Group C
Reserved parameters - Group C