LOAD MODE AUTO/MANU
When the manual mode is set, the
Load/Unload function can only be
executed by pressing “load/unload’button
COM MODE BAN/COMP./BLOCK
When this is set as “BAN” the
communication function is not available
When this is set as “COMP. ”
Controller as a slave, in accordance with
MODBUS protocol communications
with external devices
When this is set block,block control
active
COM ADD 0255 Communication address
BLOCKING
MODE
SEQ STATE SLAVE
Service as main or assistant air
compressor during interlocking
operation. The MAIN controls the
SLAVE
TURN TIME 9999 Hours
During interlocking operation, if one air
compressor continuously operates for
time period more than time set here and
rest time of one air compressor in
interlocking network has reached the
time set here, alternative rest is achieved
by starting the resting air compressor and
stopping the operating air compressor
SEQ NUMER 0016
Number of air compressors in
interlocking network during interlocking
operation
SEQ LOAD *.**MPa
The main air compressor searches for one
device in the interlocking network for
loading or starting when main air
compressor’s gas supply pressure is less
than the value set here during
interlocking operation
SEQ U.L. *.**MPa
The main air compressor searches for one
device in the interlocking network for
unloading or stopping when main air
compressor’s gas supply pressure is more
than the value set here during
interlocking operation
SEQ DELAY 0030S
The least waiting time that the main air
compressor needs to continuously sends
control commands two time
CLR LIFE
TIME
OIL FILTER
0000H Reset time for the duration of oil filter
changing
O/A FILTER
0000H
Reset time for O/G Separator changing
AIR FILTER
0000H
Reset time for gas filter changing
LUBE
0000H
Reset time for Lubricate Oil Changing
GREASE
0000H Reset time for Lubricate Grease
Changing
BELT
0000H
Reset time for Belt Grease Changing
MAX LIFE
TIME
OIL FILTER
9999H Set this value to “0” will make the oil
filter alarm not available
O/A
SEPARATOR
9999H Set this value to “0” to disable the O/G
separator alarm function
AIR FILTER
9999H Set this value to “0” to disable the alarm
function of gas filter