C
COEF 1.000
Calibration current, the input coefficients.
Controller displays the current value = sample
value × COEF
CUR ***.*A
Displays the current controller sampling current
values. This value is the real value can not be
set.
10、the operating authority and password
Controller provides multiple passwords and access management, according to
different levels of passwords, providing different levels of operating authority,
different levels of passwords and permissions as follows:
1. user's password: fixed as :___________
Permissions: allows to modify the load pressure unload pressure, fan start temperature, fan stop
temperature, start and stop mode, loading method, communication mode, communication address
and linkage parameters.
2. User Password: set as:___________
3. Permissions: Allows to modify all user parameters.
4. manufacturers sales password: this password can be modify, set to :___________
Permissions: Allows users to modify all the parameters, the user password, and the
parameters of some manufacturers, manufacturers selling password.
5. manufacturers Password: factory fixed:___________
Permissions: Allows users to modify all the parameters, the user password, and the parameters of
some manufacturers, manufacturers selling password.
6. Calibration Password: set as:___________
Permissions: allows you to modify the current parameters of the calibration parameters
7. Super Password: set as:___________
Permissions:
Allows users to modify
"run time " "phase sequence protection "
"power frequency " "max run time"
2、 Technical parameters and functions
1、Digital input: Digital input of 3# circuit; digital output of relay of 5# circuit;
2、Simulation quantity: Pt100 temperature input of 1# circuit; 4~20mA input of transducer of 1# circuit; two
groups of three phase current input(CT provided);
3、Input voltage of phase sequence: three phase 380V/220V;
4、Controller’s power supply: AC20V、50Hz、10VA;
5、Measurement range displayed:
①、Oil temperature:-50~150℃; precision: ±1℃.
②、Air temperature:-50~150℃;precision:±1℃.
③、Operation time: 0~999999 hours.
④、Measurement range displayed for current:0~999.9A.
⑤、Pressure: 0~1.60MPa. Precision: 0.01Mpa.
6、Phase-sequence protection: When protector inspects wrong phase, response time≤2s (optional);
7、 Protection of motor: this controller has five basic protection functions for main motor and fan’s motor