Atomizer Not Misng
Make sure to unplug the unit while checking connecons or anything pertaining to the
electronic box and plug back in when tesng.
Possible Causes of Atomizer Failure:
1. Water Pump
2. Water Valve
3. Water Feed Hose
4. Atomizer
Troubleshoong
Step 1 Water Pump
- Unplug the Power Breezer for 30 seconds then begin to troubleshoot the pump.
- Ensure there is sufficient water to cover the intake of the pump.
- All hoses are connected correctly.
- Pick up the pump and feel for vibraon - ensuring power is geng to the pump.
a. No vibraon - check that the pump is geng 12 volts.
1. Use an E-Box wiring diagram to verify wiring (180-700-750 wiring
diagram).
2. If the wiring is correct and the motor is not turning on, replace the Motor,
retest.
b. If you feel a vibraon, the pump is working, but there is no mist, go to step 2.
Step 2 Water Valve
- Verify the blue dial on the water valve is parallel to the grey case (perpendicular will shut
- off the water).
- Pull off the water feed tube from the pump to the valve.
A. If water is not flowing, return to the pump and return to step 1.
B. If water is flowing, return the hose to the valve and remove the hose from the
other side of the valve.
1. If water is flowing, go to step 3.
2. If water is not flowing replace the valve.
Step 3 Water Feed Hose
- Using compressed Air, ( above 40 PSI) take the nozzle, blow it into the Water Feed Tube
to the Atomizer; blow into the tube for 2–3 seconds at a me. Reconnect the Water
Feed Line and test.
1. If it is misng (water flow) problem resolved.
2. If not, go to step 4.
Step 4 Analysis of the Atomizer
- Place a towel inside the atomizer catch tray to avoid losing the screws down the drain.