VS65 SERIES MV SOFT STARTER
4.7. Group 7 – G7: OUTPUTS
G7.1 / Relay 1
control source
selection
Relay will be active a fault occurs.
ON at the beginning of the ramp up /
OFF at the end of the ramp down.
Figure [G7.3]
ON at the end of the ramp up /
OFF at the beginning of the ramp down.
Figure [G7.3]
G7.2 / Relay 2
control source
selection
G7.3 / Relay 3
control source
selection
G7.4 /
Analogue
output 1 source
selection
Provides the ability to select the driving source of the Analogue output, from the following list.
G7.5 /
Analogue
output format
Select the electrical format of the Analogue output.
Note: To obtain an analogue output of 0-10V, you should configure the analogue output format
as 0-20mA and connect a resistor of 500 Ω, ¼ W and 1% between terminals 22 and 23.